Difference between revisions of "XPS50P50"

From CPS Technical Wiki
Jump to: navigation, search
(Monitor connector)
(Monitor connector)
Line 7: Line 7:
 
This connector provides access to metering output signals and the safety interlock input signal.
 
This connector provides access to metering output signals and the safety interlock input signal.
  
Pin Name   Function               Usage
+
{| class="wikitable"
--- ------  --------                -----
+
|-
1   RETURN Signal ground           Ground reference for meter outputs (kV MON, mA MON).
+
! Pin !! Name !! Function !! Usage
2   kV MON HV meter (out)         0 to +10 V = 0 to +50 kV out.
+
|-
3   mA MON Beam meter (out)       0 to +10 V = 0 to 1 mA out.
+
| 1|| RETURN|| Signal ground|| Ground reference for meter outputs (kV MON, mA MON).
4   INTLK   Safety interlock (in)   Short to pin 1 to enable HV output; leave open to disable HV output.
+
|-
 +
| 2|| kV MON|| HV meter (out)|| 0 to +10 V = 0 to +50 kV out
 +
|-
 +
| 3|| mA MON|| Beam meter (out)|| 0 to +10 V = 0 to 1 mA out
 +
|-
 +
| 4|| INTLK|| Safety interlock (in)|| Short to pin 1 to enable HV output; leave open to disable HV output
 +
|}
  
 
===Control/monitor connector===
 
===Control/monitor connector===

Revision as of 16:11, 7 December 2021

This is the wiki page for CPS model XPS50P50.

Contents

Connector pinouts

Monitor connector

This connector provides access to metering output signals and the safety interlock input signal.

Pin Name Function Usage
1 RETURN Signal ground Ground reference for meter outputs (kV MON, mA MON).
2 kV MON HV meter (out) 0 to +10 V = 0 to +50 kV out
3 mA MON Beam meter (out) 0 to +10 V = 0 to 1 mA out
4 INTLK Safety interlock (in) Short to pin 1 to enable HV output; leave open to disable HV output

Control/monitor connector

Wiring diagrams

Wiring diagrams showing local vs. remote control of model XPS50P50

Model XPS50P50 can either be controlled locally, by adjusting its internal trimpots, or remotely by connecting it to external programming voltages.